Parameters | Unit | Premier Towers | World Trade Centre | Heritage Towers | Ridge Towers | |
Air temperature-Mean value (min-max) | ˚C | 24.5 (22.5 to 25.9) | 28.4 (26.7 to 29.5) | 26.1 (24.8 to 27.7) | 24.3 (23.9 to 25.1) | |
Relative humidity-Mean value (min-max) | % | 54 (48 to 58.2 ) | 71.6 (70 to 73.3 ) | 59 (54 to 68 ) | 51.2 (50 to 52.6 ) | |
Air velocity-Mean value (min-max) | m/s | 0.1 (0 to 0.2 ) | 0.35 (0.2 to 0.5 ) | 0.11 (0 to 0.21 ) | 0.1 (0 to 0.2 ) | |
Clothing insulation | clo | Cotton working shirt with long sleeves/short sleeve, working trousers/skirt, 3piece suit. Average clothing insulation value used (0.8 clo). | ||||
PMV Mean value (min-max) | - | 0.3 (−0.02 to 0.6 ) | 1.5 (1.0 to 1.8 ) | 0.8 (0.4 to 1. 2 ) | 0.2 (0.1 to 0.4 ) | |
PPD Mean value (min-max) | % | 11 (5.5 to 18.3) | 51.4 (27.6 to 67.3) | 20.24 (9 to 38.1) | 6.28 (5.2 to 9 ) | |
AMV Mean value (min-max) | - | −0.5 (−3 to 2) | 0.5 (−2 to 3) | −0.5 (−3 to 2) | −1.5 (−3 to 0) | |